北京郊区一轮是安装的灌溉泵,流量为35m3/h,扬程25m,配用电机功率5.5kW。
故障为电机合;不上闸,泵转不起来。
解决过程:现场泵盘车车轻松灵活,轴承润滑正常,电机接线正确, 启泵时出口阀门是关闭的。但电机没有启动器降压启动,而是直按启动的。 再进一步检查,变压器离泵很远,约有1500m,并且用很细的塑料导线连接起来。看了之后觉得变压器离泵这麽远,导线又那么细,线压降一定很大,决定赶快测量电机接战端的电压,结果仅为330V,电压太低,又是直接启动,当然就起不来了。后换了粗的导线电压上升到380V,泵就起来了。渣浆泵
The first round of irrigation pump is installed in Beijing suburb, with flow of 35m3 / h, lift of 25m and motor power of 5.5kW.
The fault is that the motor is closed; the pump can't run without the brake.
Solution: the on-site pump turning gear is easy and flexible, the bearing lubrication is normal, the motor wiring is correct, and the outlet valve is closed when the pump is started. But the motor does not start with the starter reduced voltage, but with the direct press. Further inspection shows that the transformer is far away from the pump, about 1500m long, and connected with a thin plastic wire. After reading it, I felt that the transformer was so far away from the pump, the wire was so thin, and the voltage drop of the wire must be very large. I decided to measure the voltage of the motor terminal as soon as possible, and the result was only 330V. The voltage was too low, and it was started directly. Of course, it couldn't get up. After the change of the thick wire voltage rise to 380V, the pump up. Slurry pump